No.
Name / Range /
Selection
0...65535
91.33
Module 1 emulated
Z-pulse offset
0.00000 ... 1.00000
rev
91.41
Module 2 TTL output
source
Not selected
Module input 1
Module input 2
91.42
Module 2 emulation
pulses/rev
0...65535
91.43
Module 2 emulated
Z-pulse offset
0.00000 ... 1.00000
rev
Description
Number of TTL pulses for emulation.
With interface module 1, defines when zero pulses are
emulated in relation to zero position received from the
encoder.
For example, with a value of 0.50000, a zero pulse is
emulated whenever the encoder position passes 0.5
revolutions. With a value of 0.00000, a zero pulse is
emulated whenever the encoder position passes zero
position.
Position of emulated zero pulses.
Selects the encoder input on interface module 2 whose
signal is echoed by or emulated to the TTL output.
See also section
Encoder support (page
TTL output not in use.
Input 1 is echoed by or emulated to the TTL output.
Input 2 is echoed by or emulated to the TTL output.
Defines the number of TTL pulses per revolution for
encoder emulation output of interface module 2.
Number of TTL pulses for emulation.
With interface module 2, defines when zero pulses are
emulated in relation to zero position received from the
encoder.
For example, with a value of 0.50000, a zero pulse is
emulated whenever the encoder position passes 0.5
revolutions. With a value of 0.00000, a zero pulse is
emulated whenever the encoder position passes zero
position.
Position of emulated zero pulses.
Parameters 579
Def / Type
FbEq 16b / 32b
1 = 1 / 1 = 1
- / real32
32767 = 1 rev /
100000 rev
Not selected / uint16
92).
0
1
2
- / uint16
1 = 1 / 1 = 1
- / real32
32767 = 1 rev /
100000 rev