ABB ACS880 Firmware Manual page 688

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

688 Fault tracing
Code
Event name /
(hex)
Aux. code
A88E
Cabinet fan
A88F
Cooling fan
A890
Additional
cooling fan
A8A0
AI Supervised
Warning
A8B0
Signal
supervision
A8B1
Signal
supervision 2
A8B2
Signal
supervision 3
A8BE
ULC overload
A8BF
ULC
underload
Cause
Warning generated by an ontime
timer.
Programmable warnings:
33.14 On-time 1 warn message
33.24 On-time 2 warn message
Warning generated by an ontime
timer.
Programmable warnings:
33.14 On-time 1 warn message
33.24 On-time 2 warn message
Warning generated by an ontime
timer.
Programmable warnings:
33.14 On-time 1 warn message
33.24 On-time 2 warn message
An analog signal is outside the limits
specified for the analog input.
Warning generated by the signal
supervision 1 function.
Warning generated by the signal
supervision 2 function.
Warning generated by the signal
supervision 3 function.
Selected signal has exceeded the user
overload curve.
Selected signal has fallen below the
user underload curve.
What to do
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
0:
33.13 On-time 1 source
1:
33.23 On-time 2 source
10:
5.4 Main fan on-time
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
0:
33.13 On-time 1 source
1:
33.23 On-time 2 source
10:
5.4 Main fan on-time
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
0:
33.13 On-time 1 source
1:
33.23 On-time 2 source
10:
5.4 Main fan on-time
Check the auxiliary code (format XYY).
"X" specifies the location of the input
(0: AI on control unit; 1: I/O extension
module 1, etc.), "YY" specifies the input
and limit (01: AI1 under minimum, 02:
AI1 over maximum, 03: AI2 under
minimum, 04: AI2 over maximum).
Check signal level at the analog input.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter group
12 Standard
AI,
14 I/O extension
module
1,
15 I/O extension module 2
or
16 I/O extension module
Check the source of the warning
(parameter
32.7 Supervision 1
Check the source of the warning
(parameter
32.17 Supervision 2
Check the source of the warning
(parameter
32.27 Supervision 3
Check for any operating conditions
increasing the monitored signal (for
example, the loading of the motor if
the torque or current is being
monitored).
Check the definition of the load curve
(parameter group
37 User load
Check for any operating conditions
decreasing the monitored signal (for
example, loss of load if the torque or
current is being monitored).
Check the definition of the load curve
(parameter group
37 User load
counter.
counter.
counter.
3.
signal).
signal).
signal).
curve).
curve).

Hide quick links: