664 Fault tracing
Code
Event name /
(hex)
Aux. code
000E
0011
0012
001C
001D
001E
0023, 0024
002A
64B0
Memory unit
detached
64B1
Internal SSW
fault
64B2
User set fault
64E1
Kernel
overload
64FF
Fault reset
6581
Parameter
system
Cause
Program corrupted or block
non-existent.
Program too large.
Program is empty.
A nonexisting parameter or block is
used in the program.
Parameter type invalid for selected
pin.
Output to parameter failed because
the parameter was write-protected.
Program file incompatible with
current firmware version.
Too many blocks.
The memory unit was detached when
the control unit was powered.
Internal fault.
Loading of user parameter set failed
because
set is not compatible with control
program
drive was switched off during
loading.
Operating system error.
Informative fault.
Parameter load or save failed.
What to do
Restore the template program or
download the program to the drive.
Remove blocks until the error stops.
Correct the program and download
it to the drive.
Edit the program to correct the
parameter reference, or to use an
existing block.
Edit the program to correct the
parameter reference.
Check the parameter reference in
the program.
Check for other sources affecting
the target parameter.
Adapt the program to current block
library and firmware version.
Edit the program to reduce the
number of blocks.
Switch off the power to the control
unit and reinstall the memory unit.
In case the memory unit was not
actually removed when the fault
occurred, check that the memory unit
is properly inserted into its connector
and its mounting screw is tight.
Reboot the control unit (using
parameter
96.8 Control board
or by cycling power. If the problem
persists, contact your local ABB
representative.
Reboot the control unit (using
parameter
96.8 Control board
or by cycling power. If the problem
persists, contact your local ABB
representative.
Ensure that a valid user parameter set
exists. Reload if uncertain.
Reboot the control unit (using
parameter
96.8 Control board
or by cycling power. If the problem
persists, contact your local ABB
representative.
An active fault has been reset.
Try forcing a save using parameter
96.7 Parameter save
manually. Retry.
boot)
boot)
boot)