ABB ACS880 Firmware Manual page 411

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name / Range /
Selection
35.105
DOL starter status
word
b0
Start command:
b1
Delayed start
command:
b2
DOL feedback:
b3
DOL fault (-1):
b4...15
Reserved
0000h...FFFFh
35.106
DOL starter event
type
No action
Warning
Fault
Description
Status of the motor fan control logic.
Bit 1 is the control output for the fan, to be selected as
the source of, for example, a digital or relay output.
The other bits indicate the statuses of the selected
control and feedback sources, and the fault status.
This parameter is read-only.
Status of fan control source selected by 35.100.
0 = Stop requested
1 = Start requested
Fan control bit (delays observed). Select this bit as the
source of the output controlling the fan.
0 = Stopped
1 = Started
Status of fan feedback (source selected by 35.103).
0 = Stopped
1 = Running
Fault status.
0 = Fault (fan feedback missing). The action taken is
selected by 35.106.
1 = No fault
Selects the action taken when missing fan feedback is
detected by the motor fan control logic.
No action taken.
The drive generates a warning
Drive trips on
71B1 Motor
(A781 Motor
fan).
fan.
Parameters 411
Def / Type
FbEq 16b / 32b
- / uint16
1 = 1
Fault / uint16
0
1
2