384 Parameters
No.
Name / Range /
Selection
b4
Supervision 5 active
b5
Supervision 6 active
b6
Supervision 7 active
b7...15
Reserved
0000h...FFFFh
32.205
Supervision 4 action
Disabled
Low
High
Abs low
Abs high
Both
Abs both
32.206
Supervision 4 action
No action
Warning
Fault
Fault if running
32.207
Supervision 4 signal
Zero
Other [value]
32.208
Supervision 4 filter
time
Description
1 = Signal selected by parameter
signal
is outside its limits.
1 = Signal selected by parameter
signal
is outside its limits.
1 = Signal selected by parameter
signal
is outside its limits.
Selects the mode of signal supervision function 4.
Determines how the monitored signal (parameter
32.207 Supervision 4
signal) is compared to its lower
and upper limits (parameters
and
32.310 Supervision 4 high
is taken when the condition is fulfilled as selected in
parameter
32.206 Supervision 4
Signal supervision 4 is not in use.
A warning
(D20B Signal supervision
Action is taken whenever the signal rises above its
upper limit.
Action is taken whenever the absolute value of the
signal falls below its (absolute) lower limit.
Action is taken whenever the absolute value of the
signal rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low
limit or rises above its high limit.
Action is taken whenever the absolute value of the
signal falls below its (absolute) low limit or rises above
its (absolute) high limit.
Selects the action the drive takes when the value
monitored by signal supervision 4 exceeds its limits.
Note: This parameter does not affect the status
indicated by
32.200 Supervision
No action taken.
A warning
(D20B Signal supervision
The drive trips on
D103 Signal supervision
If running, the drive trips on
Selects the signal to be monitored by signal supervision
function 4.
None.
See
Terms and abbreviations (page
Defines a filter time constant for the signal monitored
by signal supervision 4.
32.217 Supervision 5
32.227 Supervision 6
32.237 Supervision 7
32.209 Supervision 4 low
respectively). The action
action.
4) is generated.
status.
4) is generated.
4.
D103 Signal supervision
169).
Def / Type
FbEq 16b / 32b
1 = 1
No action / uint16
0
1
2
3
4
5
6
No action / uint16
0
1
2
4.
3
Zero / uint32
0
0.000 s / real32