356 Parameters
No.
Name / Range /
Selection
28.91
Frequency ref act 2
-598.00 ... 598.00 Hz
28.92
Frequency ref act 3
-598.00 ... 598.00 Hz
28.96
Frequency ref act 7
-598.00 ... 598.00 Hz
28.97
Frequency ref
unlimited
-598.00 ... 598.00 Hz
Description
Displays the value of frequency reference source 2
(selected by parameter
See the control chain diagram on page 756.
This parameter is read-only.
Value of frequency reference source 2. For scaling, see
parameter 46.2.
Displays the frequency reference after the function
applied by parameter
28.13 Frequency ref1 function
any), and after selection
selection). See the control chain diagram on page 756.
This parameter is read-only.
Frequency reference after selection. For scaling, see
parameter 46.2.
Displays the frequency reference after application of
constant frequencies, control panel reference, etc. See
the control chain diagram on page 756.
This parameter is read-only.
Frequency reference 7. For scaling, see parameter 46.2.
Displays the frequency reference after application of
critical frequencies, but before ramping and limiting.
See the control chain diagram on page 757.
This parameter is read-only.
Frequency reference before ramping and limiting. For
scaling, see parameter 46.2.
28.12 Frequency ref2
source).
(28.14 Frequency ref1/2
Def / Type
FbEq 16b / 32b
- / real32
- / -
- / real32
(if
- / -
- / real32
- / -
- / real32
- / -