530 Parameters
No.
Name / Range /
Selection
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
ESP CW bit 6
Other [bit]
75.61
Current pulse speed
reference
0.0 ... 100.0%
75.62
Current pulse start
current ref
0.0 ... 300.0%
75.68
Current pulse nr of
cycles
0...30000
75.69
Current pulse cycle
time
0.0 ... 30000.0 s
75.81
Pump speed ref in
0.00 ... 598.00 Hz
75.99
Starting routines
Description
Digital input DI2
(10.2 DI delayed
Digital input DI3
(10.2 DI delayed
Digital input DI4
(10.2 DI delayed
Digital input DI5
(10.2 DI delayed
Digital input DI6
(10.2 DI delayed
Digital input/output DIO1
0).
Digital input/output DIO2
1).
Parameter
74.1 ESP control word (page
controls enable/disable status of the function.
See
Terms and abbreviations (page
Defines the speed reference used to perform current
pulse-start routine. The base value to calculate the
current pulse speed reference is parameter
nominal
speed.
Current pulse speed reference.
Defines the motor current reference used for producing
a thrust to the pump impeller.
This is active only for the time defined with parameter
75.69 Current pulse cycle
many times as set in parameter
of
cycles.
The base value to calculate the current pulse start
reference is parameter
Current pulse start current ref.
Defines the quantity of desired current pulses applied
in sequence.
Each cycle consists of a period of thrust generated by
high motor current set in parameter
start current ref
and a period of waiting together
lasting as long as set in parameter
cycle
time.
Current pulse number of cycles.
Defines the time for a period in the current pulse-start
routine.
Each cycle consists of two such periods.
Current pulse cycle time.
Defines the pump speed reference.
This parameter is read-only.
Pump speed reference.
Displays the status word of the functions controlling
ESP control program starting routines, i.e. Starting
speed, Acceleration assistance, Kick-start and Current
pulse-start.
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.2 DIO delayed
status, bit
(11.2 DIO delayed
status, bit
519), bit 6 status
169).
99.9 Motor
time. This can be repeated as
75.68 Current pulse nr
99.6 Motor nominal
current.
75.62 Current pulse
75.69 Current pulse
Def / Type
FbEq 16b / 32b
3
4
5
6
7
10
11
12
4.0% / real32
10 = 1% / 10 = 1%
100.0% / real32
10 = 1% / 10 = 1%
- / real32
1 = 1 / 1 = 1
1.0 s / real32
10 = 1 s / 10 = 1 s
0.00 Hz / real32
10 = 1 Hz / 100 = 1 Hz
- / unit16