ABB ACS880 Firmware Manual page 485

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name / Range /
Selection
Auto
Transparent
General
Torque
Speed
Frequency
Position
58.29
EFB act2 type
Auto
Transparent
General
Torque
Speed
Frequency
Position
58.30
EFB status word
transparent source
Not selected
Other [value]
58.31
EFB act1 transparent
source
Not selected
Other [value]
Description
Type/source and scaling follow the type of reference
1 selected by parameter
individual settings below for the sources and scalings.
The value selected by parameter
transparent source
is sent as actual value 1. No scaling
is applied (the 16- bit scaling is 1 = 1 unit).
The value selected by parameter
transparent source
is sent as actual value 1 with a 16-bit
scaling of 100 = 1 unit (ie. integer and two decimals).
1.10 Motor torque
is sent as actual value 1. The scaling
is defined by parameter
1.1 Motor speed used
is sent as actual value 1. The
scaling is defined by parameter
1.6 Output frequency
is sent as actual value 1. The
scaling is defined by parameter
Motor position is sent as actual value 1. See parameter
90.6 Motor position
scaled.
Selects the type/source and scaling of actual value 2
transmitted to the fieldbus network through the
embedded fieldbus interface.
Type/source and scaling follow the type of reference
2 selected by parameter
individual settings below for the sources and scalings.
The value selected by parameter
transparent source
is sent as actual value 2. No scaling
is applied (the 16- bit scaling is 1 = 1 unit).
The value selected by parameter
transparent source
is sent as actual value 2 with a 16-bit
scaling of 100 = 1 unit (ie. integer and two decimals).
1.10 Motor torque
is sent as actual value 2. The scaling
is defined by parameter
1.1 Motor speed used
is sent as actual value 2. The
scaling is defined by parameter
1.6 Output frequency
is sent as actual value 2. The
scaling is defined by parameter
Motor position is sent as actual value 1. See parameter
90.6 Motor position
scaled.
Selects the source of the status word when
Control profile
is set to Transparent.
None.
See
Terms and abbreviations (page
Selects the source of actual value 1 when
type
is set to
Transparent
None.
See
Terms and abbreviations (page
58.26 EFB ref1
type. See the
58.31 EFB act1
58.31 EFB act1
46.3 Torque
scaling.
46.1 Speed
scaling.
46.2 Frequency
scaling.
58.27 EFB ref2
type. See the
58.32 EFB act2
58.32 EFB act2
46.3 Torque
scaling.
46.1 Speed
scaling.
46.2 Frequency
scaling.
58.25
169).
58.28 EFB act1
or General.
169).
Parameters 485
Def / Type
FbEq 16b / 32b
0
1
2
3
4
5
6
Torque / uint16
0
1
2
3
4
5
6
Not selected / uint32
0
Not selected / uint32
0