404 Parameters
No.
Name / Range /
Selection
2 x Pt1000 analog
I/O
3 x Pt1000 analog
I/O
Pt1000 encoder
module 1
Pt1000 encoder
module 2
35.22
Temperature 2 fault
limit
-60...1000 °
35.23
Temperature 2
warning limit
-60...1000 °
35.24
Temperature 2 AI
source
Not selected
AI1 actual value
AI2 actual value
Other [value]
35.27
Temperature 2
calibration
-30...1000 °C
Description
As selection
1 x Pt1000 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 x Pt1000 analog
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
Pt1000 sensor connected to encoder interface 1. See
parameters
91.21 Module 1 temp sensor type
Module 1 temp filter
time.
Note: Pt1000 sensor is supported with FEN-11 and
FEN-31 encoder modules only.
Pt1000 sensor connected to encoder interface 2. See
parameters
91.24 Module 2 temp sensor type
Module 2 temp filter
time.
Note: Pt1000 sensor is supported with FEN-11 and
FEN-31 encoder modules only.
Defines the fault limit for temperature monitoring
function 2.
When measured temperature 2 exceeds the limit, the
drive trips on fault
4982 External temperature
The unit is selected by parameter
Note: With °F, the range is -76...1832. With a PTC sensor,
the range is 0...5000 ohms.
Fault limit for temperature monitoring function 2.
Defines the warning limit for temperature monitoring
function 2. When measured temperature 2 exceeds the
limit, a warning
(A492 External temperature
The unit is selected by parameter
Note: With °F, the range is -76...1832. With a PTC sensor,
the range is 0...5000 ohms.
Warning limit for temperature monitoring function 2.
Selects the input for parameter
source, selections
KTY84 analog
I/O,
2 x Pt100 analog
I/O,
Direct
temperature.
None.
Analog input AI1 on the control unit.
Analog input AI2 on the control unit.
See
Terms and abbreviations (page
Defines the calibration of temperature 2.
See parameter
35.17 Temperature 1
Calibration of temperature 2 in celsius.
I/O, but with two sensors
I/O, but with three
and
and
2.
96.16 Unit
selection.
2) is generated.
96.16 Unit
selection.
35.21 Temperature 2
I/O,
1 x Pt100 analog
3 x Pt100 analog I/O
and
169).
calibration.
Def / Type
FbEq 16b / 32b
14
15
16
91.22
17
91.25
130 ° / real32
1 = 1 ° / 1 = 1 °
110 ° / real32
1 = 1 ° / 1 = 1 °
Not selected / uint32
0
1
2
0 °C / real32
1 = 1 °C / 1 = 1 °C