No.
Name / Range /
Selection
KTY84 analog I/O
KTY84 encoder
module 1
KTY84 encoder
module 2
1 x Pt100 analog I/O
2 x Pt100 analog I/O
3 x Pt100 analog I/O
Description
KTY84 sensor connected to the analog input selected
by parameter
35.14 Temperature 1 AI source
analog output. The input and output can be on the drive
control unit or on an extension module.
The following settings are required:
Set the hardware jumper or switch related to the
analog input to U (voltage). Any change must be
validated by a control unit reboot.
Set the unit selection parameter of the input to
volt.
Set the source selection parameter of the analog
output to
"Force KTY84
Select the analog input in parameter 35.14. In case
the input is located on an I/O extension module,
use selection Other (see
abbreviations (page
input value parameter (for example,
actual
value).
The analog output feeds a constant current through
the sensor. As the resistance of the sensor changes
along with its temperature, the voltage over the sensor
changes. The voltage is read by the analog input and
converted into degrees.
KTY84 sensor connected to encoder interface 1.
See also parameters
91.21 Module 1 temp sensor type
and
91.22 Module 1 temp filter
KTY84 sensor connected to encoder interface 2.
See also parameters
91.24 Module 2 temp sensor type
and
91.25 Module 2 temp filter
Pt100 sensor connected to a standard analog input
selected by parameter
and an analog output. The input and output can be on
the drive control unit or on an extension module.
The required settings are the same as with selection
KTY84 analog
I/O, except that the source selection
parameter of the analog output must be set to
Pt100
excitation.
As selection
1 x Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 x Pt100 analog
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
and an
excitation".
Terms and
20)) to point at the actual
14.26 AI1
time.
time.
35.14 Temperature 1 AI source
I/O, but with two sensors
I/O, but with three
Parameters 399
Def / Type
FbEq 16b / 32b
2
3
4
5
Force
6
7

Hide quick links: