35.30
FPTC configuration
word
b0
Module in slot 1
b1
Disable slot 1
warning
b2
Module in slot 2
b3
Disable slot 2
warning
b4
Module in slot 3
b5
Disable slot 3
warning
b6...15
Reserved
0000h...FFFFh
35.50
Motor ambient
temperature
-60...100 °
Description
Activates FPTC-xx thermistor protection modules
installed on the control unit of the drive. Using this
word, it is also possible to suppress the warnings (but
not faults) from each module.
1 = Yes: Module installed in slot 1.
1 = Yes: Warnings from the module in slot 1 suppressed.
1 = Yes: Module installed in slot 2.
1 = Yes: Warnings from the module in slot 2 suppressed.
1 = Yes: Module installed in slot 3.
1 = Yes: Warnings from the module in slot 3 suppressed.
Defines the ambient temperature of the motor for the
motor thermal protection model. The unit (°C or °F) is
selected by parameter
The motor thermal protection model estimates the
motor temperature on the basis of parameters
35.50...35.55. The motor temperature increases if it
operates in the region above the load curve, and
decreases if it operates in the region below the load
curve.
WARNING!
The model cannot protect the motor if the
motor does not cool properly because of dust,
dirt, etc.
Ambient temperature.
96.16 Unit
selection.
Parameters 405
Def / Type
FbEq 16b / 32b
- / uint16
1 = 1
20 ° / real32
1 = 1 ° / 1 = 1 °