ABB ACS880 Firmware Manual page 591

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name / Range /
Selection
94.30
Reactive power
reference
-3276.8 ... 3276.7
kVAr
94.31
Reactive power ref
source
Zero
User ref
Other [value]
94.32
User reactive power
reference
-3276.8 ... 3276.7
kVAr
94.40
Power mot limit on
net loss
0.00 ... 600.00 %
94.41
Power gen limit on
net loss
-600.00 ... 0.00 %
Description
(Only visible when IGBT supply unit control activated
by
)
95.20
Displays the reactive power reference sent to the supply
unit.
Note: This parameter is read-only.
Reactive power reference sent to the supply unit.
(Only visible when IGBT supply unit control activated
by
95.20
)
Selects the source of the reactive power reference to
be sent to the supply unit.
None.
94.32 User reactive power
See
Terms and abbreviations (page
(Only visible when IGBT supply unit control activated
by
95.20
)
Defines the reactive power reference for the supply
unit when
94.31 Reactive power ref source
ref.
User reactive power reference.
Defines the maximum shaft power for motoring mode
upon a supply network failure when IGBT supply unit
control is active (bit 15 of
on).
The value is given in percent of nominal motor power.
Note: With a diode supply unit (bit 11 of
the motoring shaft power is limited to 2% upon a
network failure regardless of this parameter.
Maximum shaft power for motoring mode upon a
supply network failure.
Defines the maximum shaft power for generating upon
a supply network failure when supply unit control is
active (bit 15 of
95.20 HW options word 1
The value is given in percent of nominal motor power.
Note: With a diode supply unit (bit 11 of
the motoring shaft power is limited to 2% upon a
network failure regardless of this parameter.
Maximum shaft power for generating mode upon a
supply network failure.
reference.
169).
is set to
95.20 HW options word 1
95.20
is on),
is on).
95.20
is on),
Parameters 591
Def / Type
FbEq 16b / 32b
- / real32
10 = 1 kVAr / 10 = 1
kVAr
User ref / uint32
0
1
0.0 kVAr / real32
User
10 = 1 kVAr / 10 = 1
kVAr
600.00 % / real32
is
1 = 1 % / 100 = 1 %
-600.00 % / real32
1 = 1 % / 100 = 1 %