No.
Name / Range /
Selection
In1P Start; In2 Stop
In1P Start; In2 Stop;
In3 Dir
In1P Start fwd; In2P
Start rev; In3 Stop
Control panel
Description
The sources of the start and stop commands are
selected by parameters
Ext2 in2
source.
The state transitions of the source bits are interpreted
as follows:
State of source 1
State of source 2
(20.8)
0?1
Any
Note: The start signal is always edge-triggered with
this setting regardless of parameter
trigger
type.
The sources of the start and stop commands are
selected by parameters
Ext2 in2
source.
The source selected by
determines the direction. The state transitions of the
source bits are interpreted as follows:
State of
State of
source 1
source 2
(20.8)
(20.9)
0?1
1
0?1
1
Any
0
Note: The start signal is always edge-triggered with
this setting regardless of parameter
trigger
type.
The sources of the start and stop commands are
selected by parameters
in2 source
and
20.10 Ext2 in3
transitions of the source bits are interpreted as follows:
State of
State of
source 1
source 2
(20.8)
(20.9)
0?1
Any
Any
0?1
Any
Any
Note: The start signal is always edge-triggered with
this setting regardless of parameter
trigger
type.
The start and stop commands are taken from the
control panel.
20.8 Ext2 in1 source
and
Command
(20.9)
1
Start
0
Stop
20.7 Ext2 start
20.8 Ext2 in1 source
and
20.10 Ext2 in3 source
State of
Command
source 3
(20.10)
0
Start forward
1
Start reverse
Any
Stop
20.7 Ext2 start
20.8 Ext2 in1
source,
20.9 Ext2
source. The state
State of
Command
source 3
(20.10)
1
Start forward
1
Start reverse
0
Stop
20.7 Ext2 start
Parameters 283
Def / Type
FbEq 16b / 32b
4
20.9
5
20.9
6
11