32 Quick start-up guide
Ensure that the Safe torque off and emergency stop circuits (if present) are closed.
Start the identification run by pressing the
(Start) button.
Check that the motor runs in the correct direction (forward direction shown below).
The identification run has completed when the drive stops and the value of parameter
99.13 reverts to "No".
If the motor ran in the wrong direction, correct the motor cabling or adjust parameter
99.16 Phase order.
Check the positions of jumpers J1 and J2 on the control unit of the drive. These jumpers
determine whether analog inputs AI1 and AI2 are current or voltage.
Check/adjust the following parameters.
20.01 Ext1 commands
By default, the drive starts/stops according to the status of digital input DI1 (0 = Stop,
1 = Start). DI2 determines the direction of rotation (0 = Forward, 1 = Reverse).
If other sources are required, change the value accordingly. The sources In1...In3 are
defined by parameters 20.03...20.05.
12.15 AI1 unit selection
Set this to either mA or V corresponding to the setting of jumper J1.
2 – Supply voltage and motor data settings
3 – Control signal settings
A warning will indicate that the identific-
ation run is in progress.