60.7
M/F link control
1...15
60.8
M/F comm loss
timeout
0 ms
60.9
M/F comm loss
function
NoAction
Warning
Fault
Fault always
60.10
M/F ref1 type
Auto
Torque
Description
Defines the light intensity of the transmission LED of
RDCO module channel CH2. (This parameter is effective
only when parameter
60.1 M/F communication port
set to
RDCO CH
2. FDCO modules have a hardware
transmitter current selector.)
In general, use higher values with longer fiber optic
cables.
The maximum setting is applicable to the maximum
length of the fiber optic link. See
functionality (page
72).
Light intensity.
Sets a timeout for master/follower (DDCS)
communication. If a communication break lasts longer
than the timeout, the action specified by parameter
60.9 M/F comm loss function
As a rule of thumb, this parameter should be set to at
least 3 times the transmit interval of the master.
Master/follower communication timeout.
Selects how the drive reacts to a master/follower
communication break.
No action taken.
The drive generates an
This only occurs if control is expected from the
master/follower link, or if supervision is forced using
parameter
60.32 M/F comm supervision
WARNING!
Make sure that it is safe to continue operation
in case of a communication break.
Drive trips on
7582 M/F comm
control is expected from the master/follower link, or
if supervision is forced using parameter
comm supervision
force.
Drive trips on
7582 M/F comm
though no control is expected from the master/follower
link.
Selects the type and scaling of reference 1 received
from the master/follower link. The resulting value is
shown by
3.13 M/F or D2D
Type and scaling are chosen automatically according
to which reference chain (see settings Torque, Speed,
Frequency) the incoming reference is connected to. If
the reference is not connected to any chain, no scaling
is applied (as with setting Transparent).
No scaling is applied.
Generic reference with a scaling of 100 = 1 (ie. integer
and two decimals).
The scaling is defined by parameter
Master/follower
is taken.
A7CB M/F comm loss
warning.
force.
loss. This only occurs if
60.32 M/F
loss. This occurs even
ref1.
46.3 Torque
Parameters 491
Def / Type
FbEq 16b / 32b
10 / uint16
is
- / -
100 ms / uint16
- / -
Fault / uint16
0
1
2
3
Auto / uint16
0
1
2
scaling.
3