528 Parameters
No.
Name / Range /
Selection
75.25
Deceleration time 2
0.0 ... 1800.0 s
75.40
Acceleration
assistance enable
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
ESP CW bit 4
Other [bit]
75.42
Acceleration
assistance speed
limit
0.0 ... 100.0%
75.46
Acceleration
assistance current
0.0 ... 300.0%
75.50
Kick start enable
Description
Defines the time for the pump-motor to decelerate
from the speed set in parameter
down to 0.
Note: If parameter
75.23 Ramp switch speed
greater than 0, then this parameter ramp time setting
is used while speed reference is in lower speed region.
Deceleration time 2 in seconds.
Defines the source for Acceleration assistance enable
signal.
For further information, see section Acceleration
assistance .
Acceleration assistance is inactive.
Acceleration assistance is active.
Digital input DI1
(10.2 DI delayed
Digital input DI2
(10.2 DI delayed
Digital input DI3
(10.2 DI delayed
Digital input DI4
(10.2 DI delayed
Digital input DI5
(10.2 DI delayed
Digital input DI6
(10.2 DI delayed
Digital input/output DIO1
0).
Digital input/output DIO2
1).
Parameter
74.1 ESP control word (page
controls enable/disable status of the function.
See
Terms and abbreviations (page
Defines the speed limit at which acceleration assistance
is automatically disabled.
The assistance current boost is produced only once. If
the speed is below the value set in the parameter, then
no repeated current boost is applied.
Acceleration assistance speed limit.
Defines motor current reference used when the
acceleration assistance routine is active. The base value
to calculate the acceleration assistance current is
parameter
99.6 Motor nominal
Acceleration assistance current.
Defines the source for Kick-start enable signal.
Note: If used with step-up transformer, Kick-start
function provides pre-magnetization for the motor to
increase starting torque. Else, it can be used to improve
the motor performance during start.
For further information, see section Kick-start .
46.2 Frequency scaling
is set to
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.2 DIO delayed
status, bit
(11.2 DIO delayed
status, bit
519), bit 4 status
169).
current.
Def / Type
FbEq 16b / 32b
30.0 s / real32
1 = 1 s / 10 = 1 s
ESP CW bit 4 / unit32
0
1
2
3
4
5
6
7
10
11
12
20.0% / real32
10 = 1% / 10 = 1%
100.0% / real32
10 = 1% / 10 = 1%
ESP CW bit 5 / unit32