ABB ACS880 Firmware Manual page 293

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name / Range /
Selection
21.5
Emergency stop
source
Active (false)
Inactive (true)
DIIL
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
21.6
Zero speed limit
0.00 ... 30000.00
rpm
Description
Selects the source of the emergency stop signal. The
stop mode is selected by parameter
stop
mode.
0 = Emergency stop active
1 = Normal operation
Note: This parameter cannot be changed while the
drive is running.
0.
1.
DIIL input
(10.2 DI delayed
Digital input DI1
(10.2 DI delayed
Digital input DI2
(10.2 DI delayed
Digital input DI3
(10.2 DI delayed
Digital input DI4
(10.2 DI delayed
Digital input DI5
(10.2 DI delayed
Digital input DI6
(10.2 DI delayed
Digital input/output DIO1
0).
Digital input/output DIO2
1).
See
Terms and abbreviations (page
Defines the zero speed limit. The motor is stopped
along a speed ramp (when ramped stop is selected)
until the defined zero speed limit is reached. After the
zero speed delay, the motor coasts to a stop.
Note: If you use a value below the default, make sure
the drive is able to stop.
Zero speed limit. For scaling, see parameter 46.1.
21.4 Emergency
status, bit 15).
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.2 DIO delayed
status, bit
(11.2 DIO delayed
status, bit
169).
Parameters 293
Def / Type
FbEq 16b / 32b
Inactive (true); DI4
(95.20 b1, 95.20 b2) /
uint32
0
1
2
3
4
5
6
7
8
11
12
30.00 rpm / real32
- / -

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents