ABB ACS880 Firmware Manual page 553

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name / Range /
Selection
b6
Allow current pulse
b7
Acceleration boost
b8...9
Reserved
b10
Max cleaning
supervision
b11
Supervision low
b12
Supervision high
b13
Reserved
b14
Manual trig level
b15
Invert ref sign
0000h...FFFFh
81.11
Manual trigger
source
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
Description
Enables current pulse start mode. See parameter
Current pulse start mode
Enables cleaning acceleration boost. See parameter
81.35 Acceleration boost
Enables supervision for the maximum allowed number
of cleaning.
Allows low level supervision automatically interrupt the
pump cleaning procedure.
Allows high level supervision to skip current cleaning
step cycle.
Sets use-style of the manual trigger to initiate pump
cleaning procedure on source signal level.
Invert cleaning procedure speed reference sign for the
both steps.
Defines source for the Manual trigger signal necessary
to activate the cleaning operation.
To activate triggering option, set parameter
Pump cleaning option sel
Note: The triggering style can be controlled with
parameter
81.02 Pump cleaning option
There are two possible use cases for cleaning manual
trigger.
When bit-14 is set to 0, cleaning function request
is created only on the rising edge of the source
signal. Note, that the trigger signal must remain
ON for the cleaning request.
When bit-14 is set to 1, cleaning function request
is defined by the source signal level status. If the
trigger signal is ON all the time, then cleaning
operation will be performed at every start.
Manual trigger source is not selected.
Manual trigger source is selected.
Digital input DI1
(10.2 DI delayed
Digital input DI2
(10.2 DI delayed
Digital input DI3
(10.2 DI delayed
Digital input DI4
(10.2 DI delayed
Digital input DI5
(10.2 DI delayed
Digital input DI6
(10.2 DI delayed
Digital input/output DIO1
0).
enable.
current.
81.02
to bit 1.
sel, bit-14.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.2 DIO delayed
status, bit
Parameters 553
Def / Type
FbEq 16b / 32b
75.60
1 = 1
ESP CW bit 12 /
unit32
0
1
2
3
4
5
6
7
10