504 Parameters
No.
Name / Range /
Selection
Auto
Torque
Speed
Frequency
60.63
DDCS controller act2
type
Auto
Auto
Auto
Torque
Speed
Frequency
60.64
Mailbox dataset
selection
0...1
60.65
DDCS controller
comm supervision
force
b0
Ext 1
b1
Ext 2
b2
Local
b3...15
Reserved
0000h...FFFFh
Description
Type/source and scaling follow the type of reference
1 selected by parameter
type. See the individual settings below for the sources
and scalings.
Reserved.
Reserved.
1.10 Motor torque
is sent as actual value 1. The scaling
is defined by parameter
1.1 Motor speed used
is sent as actual value 1. The
scaling is defined by parameter
1.6 Output frequency
is sent as actual value 1. The
scaling is defined by parameter
Selects the type/source and scaling of actual value
ACT2 transmitted to the external controller.
Type/source and scaling follow the type of reference
2 selected by parameter
type. See the individual settings below for the sources
and scalings.
Reserved.
Reserved.
1.10 Motor torque
is sent as actual value 2. The scaling
is defined by parameter
1.1 Motor speed used
is sent as actual value 2. The
scaling is defined by parameter
1.6 Output frequency
is sent as actual value 2. The
scaling is defined by parameter
Selects the pair of data sets used by the mailbox service
in the drive/controller communication.
See section
External controller interface (page
Data sets 32 and 33.
Activates DDCS controller communication monitoring
separately for each control location (see section
control vs. external control (page
The parameter is primarily intended for monitoring the
communication with the controller when it is connected
to the application program and not selected as a
control source by drive parameters.
1 = Communication monitoring active when Ext 1 is
being used.
1 = Communication monitoring active when Ext 2 is
being used.
1 = Communication monitoring active when local
control is being used.
60.60 DDCS controller ref1
46.3 Torque
scaling.
46.1 Speed
scaling.
46.2 Frequency
scaling.
60.61 DDCS controller ref2
46.3 Torque
scaling.
46.1 Speed
scaling.
46.2 Frequency
scaling.
39).
Def / Type
FbEq 16b / 32b
0
1
2
3
4
5
Auto / uint16
0
1
2
3
4
5
0 / uint16
81).
- / -
- / uint16
Local
1 = 1