ABB ACS880 Firmware Manual page 252

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

252 Parameters
No.
Name / Range /
Selection
14.45
AI2 unit selection
mA
V
14.46
AI2 filter gain
No filtering
125 us
250 us
500 us
1 ms
2 ms
4 ms
7.9375 ms
Description
(Visible when
14.1 Module 1 type
Selects the unit for readings and settings related to
analog input AI2.
Note: This setting must match the corresponding
hardware setting on the I/O extension module (see the
manual of the I/O extension module). The hardware
setting is shown by parameter
position. I/O module reboot either by cycling the power
or through parameter
required to validate any changes in the hardware
settings.
Milliamperes.
Volts.
(Visible when
14.1 Module 1 type
Selects a hardware filtering time for AI2.
See also parameter
14.47 AI2 filter
No filtering.
125 microseconds.
250 microseconds.
500 microseconds.
1 millisecond.
2 milliseconds.
4 milliseconds.
7.9375 milliseconds.
= FAIO-01)
14.44 AI2 HW switch
96.8 Control board boot
= FAIO-01)
time.
Def / Type
FbEq 16b / 32b
mA / uint16
is
10
2
1 ms / uint16
0
1
2
3
4
5
6
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents