No.
Name / Range /
Selection
26.56
Oscillation damping
phase
0...360 deg
26.57
Oscillation damping
gain
0.0 ... 100.0 %
26.58
Oscillation damping
output
-1600.000 ...
1600.000 %
26.70
Torque reference act
1
-1600.0 ... 1600.0 %
26.71
Torque reference act
2
-1600.0 ... 1600.0 %
26.72
Torque reference act
3
-1600.0 ... 1600.0 %
26.73
Torque reference act
4
Description
Defines a phase shift for the output of the filter.
Note: Before changing this parameter run-time, disable
the oscillation damping output using parameter 26.52.
Monitor the behavior of
output.
Phase shift for oscillation damping function output.
Defines a gain for the output of the oscillation damping
function, ie. how much the output of the filter is
amplified before it is added to the torque reference.
Oscillation gain is scaled according to the speed
controller gain so that changing the gain will not
disturb oscillation damping.
Note: Before changing this parameter run-time, disable
the oscillation damping output using parameter 26.52.
Monitor the behavior of
output.
Gain setting for oscillation damping output.
Displays the output of the oscillation damping function.
This value is added to the torque reference (as allowed
by parameter
26.52 Oscillation damping out
This parameter is read-only.
Output of the oscillation damping function.
Displays the value of torque reference source 1
(selected by parameter
the control chain diagram on page 751.
This parameter is read-only.
Value of torque reference source 1. For scaling, see
parameter 46.3.
Displays the value of torque reference source 2
(selected by parameter
the control chain diagram on page 751.
This parameter is read-only.
Value of torque reference source 2. For scaling, see
parameter 46.3.
Displays the torque reference after the function applied
by parameter
26.13 Torque ref1 function
after selection
(26.14 Torque ref1/2
control chain diagram on page 751.
This parameter is read-only.
Torque reference after selection. For scaling, see
parameter 46.3.
Displays the torque reference after application of
reference additive 1. See the control chain diagram on
page 751.
This parameter is read-only.
26.58
before re-enabling the
26.58
before re-enabling the
enable).
26.11 Torque ref1
source). See
26.12 Torque ref2
source). See
(if any), and
selection). See the
Parameters 345
Def / Type
FbEq 16b / 32b
180 deg / real32
10 = 1 deg / 1 = 1 deg
1.0 % / real32
10 = 1 % / 10 = 1 %
- / real32
10 = 1 % / 1000 = 1 %
- / real32
- / -
- / real32
- / -
- / real32
- / -
- / real32