ABB ACS880 Firmware Manual page 184

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

184 Parameters
No.
Name / Range /
Selection
4.22
Fault word 2
Description
ACS800-compatible fault word 2.
The bit assignments of this word correspond to FAULT
WORD 2 in the ACS800. Parameter
word compatibility
determines whether the bit
assignments are according to the ACS800 Standard or
ACS800 System control program.
Each bit can indicate several ACS880 events as listed
below.
This parameter is read-only.
ACS880 fault name
(4.120
=
ACS800
Bit
Standard ctrl
program)
0
SUPPLY
PHASE
1
NO MOT DATA
2
DC UNDER-
VOLT
3
Reserved
4
RUN ENABLE
5
ENCODER ERR
6
I/O COMM
7
CTRL B TEMP
8
EXTERNAL
FLT
9
OVER SW-
FREQ
10
AI < MIN FUNC
11
PPCC LINK
12
COMM MOD-
ULE
13
PANEL LOSS
14
MOTOR STALL
15
MOTOR
PHASE
4.120 Fault/Warning
ACS880
events indic-
(4.120
=
ated by this
ACS800 Sys-
bit
tem ctrl pro-
(see
Fault tra-
gram)
cing(page649).
SUPPLY
3130
PHASE
NO MOTOR
-
DATA
DC UNDER-
3220
VOLT
CABLE TEMP
4000
RUN DISABLE
AFEB
ENCODER ERR
7301, 7380,
7381, 73A0,
73A1
IO COMM ERR
7080,
7082
CTRL B TEMP
-
SELECTABLE
9082
OVER SW-
-
FREQ
AI<MIN FUNC
80A0
PPCC LINK
5681, 5682,
5690, 5691,
5692, 5693,
5694,
5695
COMM MOD-
6681, 7510,
ULE
7520,
7581
PANEL LOSS
7081
MOTOR STALL
7121
MOTOR
3381
PHASE
Def / Type
FbEq 16b / 32b
- / uint16

Hide quick links:

Advertisement

Table of Contents
loading