400 Parameters
No.
Name / Range /
Selection
PTC DI6
PTC analog I/O
PTC encoder module
1
PTC encoder module
2
Direct temperature
1 x Pt1000 analog
I/O
2 x Pt1000 analog
I/O
3 x Pt1000 analog
I/O
Pt1000 encoder
module 1
Description
PTC sensor connected to digital input DI6 (see the
connection diagram on page 128).
Note: Either 0 ohm (normal temperature) or 4000 ohm
(excessive temperature) will be shown by
temperature
1. By default, an excessive temperature
will generate a warning as per parameter
Temperature 1 warning
set
35.12 Temperature 1 fault limit
PTC sensor connected to a standard analog input
selected by parameter
and an analog output. The input and output can be on
the drive control unit or on an extension module.
The required settings are the same as with selection
KTY84 analog
I/O, except that the source selection
parameter of the analog output must be set to
PTC
excitation.
PTC sensor connected to encoder interface 1.
See also parameters
91.21 Module 1 temp sensor type
and
91.22 Module 1 temp filter
PTC sensor connected to encoder interface 2.
See also parameters
91.24 Module 2 temp sensor type
and
91.25 Module 2 temp filter
The temperature is taken from the source selected by
parameter
35.14 Temperature 1 AI
the source is assumed to be in the unit of temperature
specified by
96.16 Unit
Pt1000 sensor connected to a standard analog input
selected by parameter
and an analog output. The input and output can be on
the drive control unit or on an extension module.
The required settings are the same as with selection
KTY84 analog
I/O, except that the source selection
parameter of the analog output must be set to
Pt1000
excitation.
As selection
1 x Pt1000 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 x Pt1000 analog
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
Pt1000 sensor connected to encoder interface 1. See
parameters
91.21 Module 1 temp sensor type
Module 1 temp filter
time.
Note: Pt1000 sensor supports FEN-11 and FEN-31
encoder modules only.
35.2 Measured
35.13
limit. If you want a fault instead,
to 4000 ohm.
35.14 Temperature 1 AI source
time.
time.
source. The value of
selection.
35.14 Temperature 1 AI source
I/O, but with two sensors
I/O, but with three
and
Def / Type
FbEq 16b / 32b
8
20
Force
9
10
11
13
Force
14
15
16
91.22