176 Parameters
No.
Name / Range /
Selection
1.25
INU momentary cos
φ
-1.00 ... 1.00
1.29
Speed change rate
-15000...15000
rpm/s
1.30
Nominal torque
scale
0.000 ...
4000000.000 Nm or
lb·ft
1.31
Ambient
temperature
-40.0 ... 200.0 °
1.32
Inverter GWh
regenerating
0...32767 GWh
1.33
Inverter MWh
regenerating
0...1000 MWh
1.34
Inverter kWh
regenerating
0...1000 kWh
1.35
Mot - regen energy
GWh (resettable)
-32768...32767 GWh
Description
Momentary cosphi of the drive.
Cosphi.
Rate of actual speed change. Positive values indicate
acceleration, negative values indicate deceleration.
See also parameters
31.32 Emergency ramp
31.33 Emergency ramp supervision
stop supervision
and
31.38 Ramp stop supervision
delay.
Rate of speed change.
Torque that corresponds to 100% of nominal motor
torque. The unit is selected by parameter
selection.
Note: This value is copied from parameter
nominal torque
if entered. Otherwise the value is
calculated from other motor data.
Nominal torque.
Measured temperature of incoming cooling air. The
unit (°C or °F) is selected by parameter
selection.
Cooling air temperature.
Amount of energy that has passed through the drive
(towards the supply) in full gigawatt-hours. The
minimum value is zero.
Regenerative energy in GWh.
Amount of energy that has passed through the drive
(towards the supply) in full megawatt-hours. Whenever
the counter rolls over,
is incremented. The minimum value is zero.
Regenerative energy in MWh.
Amount of energy that has passed through the drive
(towards the supply) in full kilowatt-hours. Whenever
the counter rolls over,
is incremented. The minimum value is zero.
Regenerative energy in kWh.
Amount of net energy (motoring energy - regenerating
energy) that has passed through the drive in full
gigawatt hours.
You can reset the value by setting it to zero. Resetting
any of the parameters
Energy balance in GWh.
supervision,
delay,
31.37 Ramp
96.16 Unit
99.12 Motor
96.16 Unit
1.32 Inverter GWh regenerating
1.33 Inverter MWh regenerating
1.35
to
1.37
resets all.
Def / Type
FbEq 16b / 32b
0.00 / real32
100 = 1 / 100 = 1
- / real32
1 = 1 rpm/s / 1 = 1
rpm/s
0.000 Nm or lb·ft /
uint32
1 = 1 Nm or lb·ft /
1000 Nm or lb·ft
- / real32
1 = 1 ° / 10 = 1 °
- / int16
1 = 1 GWh / 1 = 1 GWh
- / int16
1 = 1 MWh / 1 = 1 MWh
- / real32
10 = 1 kWh / 1 = 1 kWh
0 GWh / int16
1 = 1 GWh / 1 = 1 GWh