ABB ACS880 Firmware Manual page 673

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Event name /
(hex)
Aux. code
A492
External
temperature 2
A497
Motor
temperature 1
A498
Motor
temperature 2
A499
Motor
temperature 3
A4A0
Control board
temperature
1
A4A9
Cooling
A4B0
Excess
temperature
Cause
Measured temperature 2 has exceeded
warning limit.
The thermistor protection module
installed in slot 1 indicates
overtemperature.
The thermistor protection module
installed in slot 2 indicates
overtemperature.
The thermistor protection module
installed in slot 3 indicates
overtemperature.
Control unit temperature is excessive.
Temperature above warning limit.
Thermistor broken.
Drive module temperature is
excessive.
Power unit temperature is excessive.
Fault tracing 673
What to do
Check the value of parameter
Measured temperature
Check the cooling of the motor (or
other equipment whose temperature
is being measured).
Check the value of
35.23 Temperature
2 warning
limit.
Check the cooling of the motor.
Check the motor load and drive
ratings.
Check the wiring of the temperature
sensor. Repair wiring if faulty.
Measure the resistance of the sensor.
Replace sensor if faulty.
Check the cooling of the motor.
Check the motor load and drive
ratings.
Check the wiring of the temperature
sensor. Repair wiring if faulty.
Measure the resistance of the sensor.
Replace sensor if faulty.
Check the cooling of the motor.
Check the motor load and drive
ratings.
Check the wiring of the temperature
sensor. Repair wiring if faulty.
Measure the resistance of the sensor.
Replace sensor if faulty.
Check the auxiliary code. See actions
for each code below.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Contact an ABB service
representative for control unit
replacement.
Check ambient temperature. If it
exceeds 40 °C (104 °F), ensure that
load current does not exceed derated
load capacity of drive. See appropriate
Hardware manual.
Check drive module cooling air flow
and fan operation.
Check inside of cabinet and heatsink
of drive module for dust pick-up. Clean
whenever necessary.
Check ambient conditions.
Check air flow and fan operation.
Check the setting of
31.36 Aux fan fault
function
(if present).
Check heatsink fins for dust pick-up.
35.3