Name / Range /
Selection
22.54
Critical speed 2 low
-30000.00 ...
30000.00 rpm
22.55
Critical speed 2 high
-30000.00 ...
30000.00 rpm
22.56
Critical speed 3 low
-30000.00 ...
30000.00 rpm
22.57
Critical speed 3 high
-30000.00 ...
30000.00 rpm
22.71
Motor
potentiometer
function
Disabled
Enabled (init at
stop/power-up)
Enabled (resume
always)
22.72
Motor
potentiometer initial
value
-32768.00 ...
32767.00
Description
Defines the low limit for critical speed range 2.
Note: This value must be less than or equal to the value
of
22.55 Critical speed 2
Low limit for critical speed 2. For scaling, see parameter
46.1.
Defines the high limit for critical speed range 2.
Note: This value must be greater than or equal to the
value of
22.54 Critical speed 2
High limit for critical speed 2. For scaling, see
parameter 46.1.
Defines the low limit for critical speed range 3.
Note: This value must be less than or equal to the value
of
22.57 Critical speed 3
Low limit for critical speed 3. For scaling, see parameter
46.1.
Defines the high limit for critical speed range 3.
Note: This value must be greater than or equal to the
value of
22.56 Critical speed 3
High limit for critical speed 3. For scaling, see
parameter 46.1.
Activates and selects the mode of the motor
potentiometer.
See section
Motor potentiometer (page
Motor potentiometer is disabled and its value set to 0.
When enabled, the motor potentiometer first adopts
the value defined by parameter
potentiometer initial
value.
When the drive is running, the value can be adjusted
from the up and down sources defined by parameters
22.73 Motor potentiometer up source
potentiometer down
source.
A stop or a power cycle will reset the motor
potentiometer to the initial value (22.72).
As
Enabled (init at
stop/power-up), but the motor
potentiometer value is retained over a stop or a power
cycle.
Defines an initial value (starting point) for the motor
potentiometer. See the selections of parameter
Motor potentiometer
function.
Initial value for motor potentiometer.
high.
low.
high.
low.
112).
22.72 Motor
and
22.74 Motor
Parameters 307
Def / Type
FbEq 16b / 32b
0.00 rpm / real32
- / -
0.00 rpm / real32
- / -
0.00 rpm / real32
- / -
0.00 rpm / real32
- / -
Disabled / uint16
0
1
2
0.00 / real32
22.71
1 = 1 / 100 = 1