Fieldbus control through the embedded fieldbus interface (EFB) 709
desired source or destination for that particular drive control signal. The
Function/Information column gives a description of the parameter.
Parameter
CONTROL COMMAND SOURCE SELECTION
20.1 Ext1 commands
20.2 Ext1 start trigger type
SPEED REFERENCE SELECTION
22.11 Speed ref1 source
22.12 Speed ref2 source
TORQUE REFERENCE SELECTION
26.11 Torque ref1 source
26.12 Torque ref2 source
FREQUENCY REFERENCE SELECTION
28.11 Frequency ref1
source
28.12 Frequency ref2
source
OTHER SELECTIONS
EFB references can be selected as the source at virtually any signal selector parameter by
selecting Other (see
reference
2.
CONTROL OF RELAY OUTPUTS, ANALOG OUTPUTS AND DIGITAL INPUT/OUTPUTS
10.24 RO1 source
10.27 RO2 source
10.30 RO3 source
Setting for fieldbus
control
Embedded fieldbus
Embedded fieldbus
EFB ref1 or EFB ref2
EFB ref1 or EFB ref2
EFB ref1 or EFB ref2
EFB ref1 or EFB ref2
EFB ref1 or EFB ref2
EFB ref1 or EFB ref2
Terms and
abbreviations), then either
RO/DIO control word
bit0
RO/DIO control word
bit1
RO/DIO control word
bit2
Function/Information
Selects fieldbus as the source for the
start and stop commands when EXT1 is
selected as the active control location.
Selects fieldbus as the source for the
start and stop commands when EXT2 is
selected as the active control location.
Selects a reference received through the
embedded fieldbus interface as speed
reference 1.
Selects a reference received through the
embedded fieldbus interface as speed
reference 2.
Selects a reference received through the
embedded fieldbus interface as torque
reference 1.
Selects a reference received through the
embedded fieldbus interface as torque
reference 2.
Selects a reference received through the
embedded fieldbus interface as fre-
quency reference 1.
Selects a reference received through the
embedded fieldbus interface as fre-
quency reference 2.
3.9 EFB reference 1
Connects bit 0 of storage parameter
10.99 RO/DIO control word
put RO1.
Connects bit 1 of storage parameter
10.99 RO/DIO control word
put RO2.
Connects bit 2 of storage parameter
10.99 RO/DIO control word
put RO3.
or
3.10 EFB
to relay out-
to relay out-
to relay out-