358 Parameters
No.
Name / Range /
Selection
0000h...FFFFh
30.2
Torque limit status
b0
Undervoltage
b1
Overvoltage
b2
Minimum torque
b3
Maximum torque
b4
Internal current
b5
Maximum load angle
b6
Motor pullout
b7
Reserved
b8
Thermal
b9
Max current
b10
User current
b11
Thermal IGBT
b12
IGBT
overtemperature
b13
IGBT overload
b14...15
Reserved
0000h...FFFFh
Description
Displays the torque controller limitation status word.
This parameter is read-only.
*Only one out of bits 0...3, and one out of bits 9...13
can be on simultaneously. The bit typically indicates
the limit that is exceeded first.
*1 = Intermediate DC circuit undervoltage
*1 = Intermediate DC circuit overvoltage
*1 = Torque is being limited by
limit,
30.27 Power generating limit
30.18 Minimum torque
*1 = Torque is being limited by
limit,
30.27 Power generating limit
30.25 Maximum torque
See diagram on page 754.
1 = An inverter current limit (identified by bits 8...11) is
active
(With permanent magnet motors, synchronous
reluctance motors, and externally-excited synchronous
motors only)
1 = Maximum load angle limit is active, ie. the motor is
producing as much torque as possible
(With asynchronous motors only)
1 = Motor pull-out limit is active, ie. the motor cannot
produce any more torque
1 = Input current is being limited by the main circuit
thermal limit
*1 = Maximum output current (I
*1 = Output current is being limited by
current
*1 = Output current is being limited by a calculated
thermal current value
*1 = Output current is being limited because of
estimated IGBT temperature
*1 = Output current is being limited because of IGBT
junction to case temperature
30.26 Power motoring
or the source of
sel. See diagram on page 754.
30.26 Power motoring
or the source of
sel.
) is being limited
MAX
30.17 Maximum
Def / Type
FbEq 16b / 32b
1 = 1
- / uint16
1 = 1