598 Parameters
No.
Name / Range /
Selection
b8
b9
b10
b11
b12...15
Reserved
0000h...FFFFh
95.20
HW options word 1
b0
Supply frequency 60
Hz
b1
Emergency stop Cat
0
b2
Emergency stop Cat
1
b3
RO2 for -07 cabinet
cooling fan
b4
Externally powered
control unit
b5
DC supply switch
b6
DOL motor switch
b7
Reserved
b8
Service switch or
PTC/Pt100 relay
b9
Output contactor
b10
Brake resistor, sine
filter, IP54 fan
Description
1 = Channel CH9 is routed to a local power unit
1 = Channel CH10 is routed to a local power unit
1 = Channel CH11 is routed to a local power unit
1 = Channel CH12 is routed to a local power unit
Specifies hardware-related options that require
differentiated parameter defaults. Activating a bit in
this parameter makes the necessary changes in other
parameters. For example, activating an emergency stop
option reserves a digital input. In many cases, the
differentiated parameters will also be write-protected.
This parameter, as well as the changes in other
parameters implemented by it, are not affected by a
parameter restore.
WARNING! After switching any bits in this word,
recheck the values of the affected parameters.
Note: This parameter cannot be changed while the
drive is running.
*See section Control of a supply unit (LSU) .
0 = 50 Hz; 1 = 60 Hz. Affects 11.45, 11.59, 12.20, 13.18,
30.11, 30.12, 30.13, 30.14, 31.26, 31.27, 40.15, 40.37, 41.15,
41.37, 46.1, 46.2.
1 = Emergency stop, Category 0, without FSO module.
Affects 21.4, 21.5, 23.11.
1 = Emergency stop, Category 1, without FSO module.
Affects 10.24, 21.4, 21.5, 23.11.
1 = Control of cabinet cooling fan (used only with
specific ACS880-07 hardware). Affects 10.27, 10.28,
10.29.
1 = Control unit powered externally. Affects 95.4. (Only
visible with a ZCU control unit)
1 = DC switch monitoring active. Affects 20.12, 31.3,
95.8. (Only visible with a ZCU control unit)
1 = Motor fan control active. Affects 10.24, 35.100,
35.103, 35.104.
1 = Service switch or PTC/Pt100 relay connected.
Affects 31.1, 31.2.
1 = Output contactor present. Affects 10.24, 20.12.
1 = Status (eg. thermal) switches connected to DIIL
input. Affects 20.11, 20.12.
Def / Type
FbEq 16b / 32b
1 = 1
- / uint16