No.
Name / Range /
Selection
95.9
Switch fuse
controller
95.12
Reduced run mask
b0
Module 1 removed
b1
Module 2 removed
b2
Module 3 removed
b3
Module 4 removed
b4
Module 5 removed
b5
Module 6 removed
b6
Module 7 removed
b7
Module 8 removed
b8
Module 9 removed
b9
Module 10 removed
b10
Module 11 removed
b11
Module 12 removed
b12...15
Reserved
0000h...FFFFh
95.13
Reduced run mode
Description
(Only visible with a BCU control unit)
Activates communication to a BSFC charging controller.
This setting is intended for use with inverter modules
that are connected to a DC bus through a DC
switch/charging circuit controlled by a charging
controller. On units without a DC switch, this parameter
should be set to Disable.
The charging controller monitors the charging of the
inverter unit, and sends an enable command when the
charging has finished (ie. DC switch is closed after the
'charging OK' lamp lights, and charging switch opened).
For more information, see BSFC documentation.
Communication with BSFC disabled.
Communication with BSFC enabled.
(Only visible with BCU control unit)
Specifies which converter modules have been removed
from the converter configuration. A value other than 0
activates the reduced run function.
See section
Reduced run function (page
Module 1 has been removed.
Module 2 has been removed.
Module 3 has been removed.
Module 4 has been removed.
Module 5 has been removed.
Module 6 has been removed.
Module 7 has been removed.
Module 8 has been removed.
Module 9 has been removed.
Module 10 has been removed.
Module 11 has been removed.
Module 12 has been removed.
(Only visible with a BCU control unit)
Specifies the number of inverter modules available.
This parameter must be set if reduced run is required.
A value other than 0 activates the reduced run function.
If the control program cannot detect the number of
modules specified by this parameter, a fault
Reduced
run) is generated.
See section
Reduced run function (page
0 = Reduced run disabled
1...12 = Number of modules available
Note: This parameter cannot be changed while the
drive is running.
Parameters 595
Def / Type
FbEq 16b / 32b
Enable / uint16
0
1
- / uint16
143).
1 = 1
- / uint16
(5695
143).