ABB ACS880 Firmware Manual page 503

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name / Range /
Selection
Speed ref safe
Fault always
Warning
60.60
DDCS controller ref1
type
Auto
Auto
Auto
Torque
Speed
Frequency
60.61
DDCS controller ref2
type
60.62
DDCS controller act1
type
Description
Drive generates an
A7CA DDCS controller comm loss
warning and sets the speed to the speed defined by
parameter
22.41 Speed ref safe
safe
when frequency reference is being used). This only
occurs if control is expected from the external
controller, or if supervision is forced using parameter
60.65 DDCS controller comm supervision
WARNING!
Make sure that it is safe to continue operation
in case of a communication break.
Drive trips on
7581 DDCS controller comm
occurs even though no control is expected from the
external controller.
Drive generates an
A7CA DDCS controller comm loss
warning. This only occurs if control is expected from
the external controller, or if supervision is forced using
parameter
60.65 DDCS controller comm supervision
force.
WARNING!
Make sure that it is safe to continue operation
in case of a communication break.
Selects the type and scaling of reference 1 received
from the external controller. The resulting value is
shown by
3.11 DDCS controller ref
Type and scaling are chosen automatically according
to which reference chain (see settings Torque, Speed,
Frequency) the incoming reference is connected to. If
the reference is not connected to any chain, no scaling
is applied (as with setting Transparent).
No scaling is applied.
Generic reference with a scaling of 100 = 1 (ie. integer
and two decimals).
The scaling is defined by parameter
The scaling is defined by parameter
The scaling is defined by parameter
scaling.
Selects the type and scaling of reference 2 received
from the external controller. The resulting value is
shown by
3.12 DDCS controller ref
For the selections, see parameter
ref1
type.
Selects the type/source and scaling of actual value
ACT1 transmitted to the external controller.
(or
28.41 Frequency ref
force.
loss. This
1.
46.3 Torque
scaling.
46.1 Speed
scaling.
46.2 Frequency
2.
60.60 DDCS controller
Parameters 503
Def / Type
FbEq 16b / 32b
3
4
5
Auto / uint16
0
1
2
3
4
5
Auto / uint16
Auto / uint16

Hide quick links:

Advertisement

Table of Contents
loading