No.
Name / Range /
Selection
0.00 ... 30000.00
rpm
46.32
Above frequency
limit
0.00 ... 1000.00 Hz
46.33
Above torque limit
0.0 ... 1600.0 %
46.42
Torque decimals
0...2
46.200
FB reference scaler
0...30000
Description
"Above limit" indication trigger level for speed control.
For scaling, see parameter 46.1.
Defines the trigger level for "above limit" indication in
frequency control. When actual frequency exceeds the
limit, bit 10 of
6.17 Drive status word 2
"Above limit" indication trigger level for frequency
control. For scaling, see parameter 46.2.
Defines the trigger level for "above limit" indication in
torque control. When actual torque exceeds the limit,
bit 10 of
6.17 Drive status word 2
"Above limit" indication trigger level for torque control.
For scaling, see parameter 46.3.
Defines the number of decimal places of torque-related
parameters.
Number of decimal places of torque parameters.
Defines the custom scaling value for fieldbus reference.
When this value is
•
set to 0, the used reference = FB ref *
20000
•
not set to 0, the used reference = FB ref
Fieldbus reference scaling value.
Parameters 455
is set.
is set.
75.19
/
/46.200
Def / Type
FbEq 16b / 32b
- / -
50.00 Hz / real32
- / -
300.0 % / real32
- / -
1 / uint16
1 = 1 / 1 = 1
0 / real32
1 = 1 / 1 = 1