No.
Name / Range /
Selection
0.000 ... 30.000 s
32.209
Supervision 4 low
-21474830.00 ...
21474830.00
32.310
Supervision 4 high
-21474830.00 ...
21474830.00
32.215
Supervision 5 action
Disabled
Low
High
Abs low
Abs high
Both
Abs both
32.216
Supervision 5 action
No action
Warning
Fault
Fault if running
32.217
Supervision 5 signal
Zero
Other [value]
32.218
Supervision 5 filter
time
Description
Signal filter time.
Defines the lower limit for signal supervision 4.
Low limit.
Defines the upper limit for signal supervision 4.
Upper limit.
Selects the mode of signal supervision function 5.
Determines how the monitored signal (parameter
Supervision 5
signal) is compared to its lower and upper
limits (parameters
32.219 Supervision 5 low
Supervision 5 high
respectively). The action is taken
when the condition is fulfilled as selected in parameter
32.216 Supervision 5
action.
Signal supervision 5 is not in use.
A warning
(D20C Signal supervision
Action is taken whenever the signal rises above its
upper limit.
Action is taken whenever the absolute value of the
signal falls below its (absolute) lower limit.
Action is taken whenever the absolute value of the
signal rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low
limit or rises above its high limit.
Action is taken whenever the absolute value of the
signal falls below its (absolute) low limit or rises above
its (absolute) high limit.
Selects the action that drive takes when the value
monitored by signal supervision 5 exceeds its limits.
Note: This parameter does not affect the status
indicated by
32.200 Supervision
No action taken.
A warning
(D20C Signal supervision
The drive trips on
80B2 Signal supervision
If running, the drive trips on
Selects the signal to be monitored by signal supervision
function 5.
None.
See
Terms and abbreviations (page
Defines a filter time constant for the signal monitored
by signal supervision 5.
32.217
and
32.320
5) is generated.
status.
5) is generated.
3.
80B2 Signal supervision
169).
Parameters 385
Def / Type
FbEq 16b / 32b
1000 = 1 s / 1000 = 1
s
0.00 / real32
- / -
0.00 / real32
- / -
No action / uint16
0
1
2
3
4
5
6
No action / uint16
0
1
2
3.
3
Zero / uint32
0
0.000 s / real32