Code
Event name /
(hex)
Aux. code
A581
Fan
A582
Auxiliary fan
not running
A5A0
Safe torque
off
A5EA
Measurement
circuit
temperature
Cause
Cooling fan feedback missing.
An auxiliary cooling fan (connected to
the fan connectors on the control unit)
is stuck or disconnected.
Safe torque off function is active, i.e.
safety circuit signal(s) connected to
connector XSTO is lost.
Problem with internal temperature
measurement of the drive.
Fault tracing 675
What to do
Check the setting of parameter
HW options word
1, bit 14.
Check the auxiliary code to identify
the fan. Code 0 denotes main fan 1.
Other codes (format XYZ): "X"
specifies state code (1: ID run, 2:
normal). "Y" specifies the index of the
inverter module connected to BCU
(0...n, always 0 for ZCU control units).
"Z" specifies the index of the fan (1:
Main fan 1, 2: Main fan 2, 3: Main fan
3).
Note that modules are coded starting
from 0. For example, the code 101
means that Main fan 1 of module 1
(connected to BCU channel V1T/V1R)
has faulted during its ID run.
Check fan operation and connection.
Replace fan if faulty.
The auxiliary code identifies the fan
(1: Auxiliary fan 1, 2: Auxiliary fan 2).
Check that the auxiliary fan
supervision selection in parameter
95.21 HW options word 2
hardware.
Make sure the front cover of the drive
module is in place and tightened.
Check auxiliary fan(s) and
connection(s).
Replace faulty fan.
Check safety circuit connections. For
more information, see appropriate
drive hardware manual and
description of parameter
indication run/stop (page
Check the auxiliary code (format XXXY
YYZZ). "Y YY" specifies through which
BCU control unit channel the fault was
received ("0 00" with a ZCU control
unit).
"ZZ" specifies the location:
With control program version 2.8x and
later: 1: U-phase IGBT, 2: V-phase IGBT,
3: W-phase IGBT, 4: Power supply
board, 5: Power unit xINT board, 6:
Brake chopper, 7: Air inlet (TEMP3,
X10), 8: du/dt filter (TEMP2, X7), 9:
TEMP1 (X6).
With control program version up to
and including 2.7x: 1: U-phase IGBT, 2:
V-phase IGBT, 3: W-phase IGBT, 4:
Power unit INT board, 5: Brake
chopper, 6: Air inlet, 7: Power supply
board, 8: du/dt filter, FAh: Air in temp.
95.20
matches the
31.22 STO
370).