736 Fieldbus control through a fieldbus adapter
Bit
Name
7
Reset
8
Inching 1
9
Inching 2
10
Remote cmd
11
Ext ctrl loc
12 to 15
Reserved.
Value
STATE/Description
0=>1
Fault reset if an active fault exists. Proceed to SWITCH-
ON INHIBITED.
Note: This bit is effective only if the fieldbus interface
is set as the source of the reset signal by drive para-
meters.
0
Continue normal operation.
1
Accelerate to inching (jogging) setpoint 1.
Note:
• Bits 4...6 must be 0.
• See also section
0
Inching (jogging) 1 disabled.
1
Accelerate to inching (jogging) setpoint 2.
See notes at bit 8.
0
Inching (jogging) 2 disabled.
1
Fieldbus control enabled.
0
Control word and reference not getting through to the
drive, except for bits 0...2.
1
Select External Control Location EXT2. Effective if
control location is parameterized to be selected from
fieldbus.
0
Select External Control Location EXT1. Effective if
control location is parameterized to be selected from
fieldbus.
Jogging (page
99).