No.
Name / Range /
Selection
99.19
Sine filter
capacitance
0.00 ... 100000.00 uF
99.200
Med-voltage side
data
Done
Calculate and apply
99.201
ESP motor nominal
current
0.0 ... 6400.0 A
Description
Defines the capacitance of a custom sine filter, i.e. when
parameter
95.15 Special HW settings
If the capacitors are star/wye-connected, enter the
capacitance of one leg into the parameter.
Drive
Sine filter
If the capacitors are delta-connected, multiply the
capacitance of one leg by 3 and enter the result into
the parameter.
Drive
Sine filter
Note: For an ABB sine filter
bit 1), this parameter is set automatically and should
not be adjusted.
Capacitance of custom sine filter.
Selects the option to calculate the required low voltage
side data.
Note: All ESP circuitry related parameters (listed below)
must be updated before this calculation.
Parameters:
95.01, 95.40, 95.200 (if known), 95.201,
95.202...95.204 (if known)
99.18, 99.19, 99.201...99.207
Requested action is completed. No more action
required.
Low voltage side data is calculated using the medium
voltage side data.
Defines nominal current of the ESP motor. This setting
must match the value on the rating plate of the motor.
Nominal current of the ESP motor.
bit 3 is activated.
M
3~
C
C
C
99.19 = C
M
3~
C
C
99.19 = 3 × C
C
(95.15 Special HW settings
Parameters 629
Def / Type
FbEq 16b / 32b
0.00 uF / real32
100 = 1 uF / 100 = 1
uF
Done / uint16
0
1
0.0 A / real32
10 = 1 A / 10 = 1 A