ABB ACS880 Firmware Manual page 452

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

452 Parameters
No.
Name / Range /
Selection
46.6
Speed ref zero
scaling
0.00 ... 30000.00
rpm
46.7
Frequency ref zero
scaling
0.00 ... 1000.00 Hz
46.11
Filter time motor
speed
0...20000 ms
46.12
Filter time output
frequency
0...20000 ms
46.13
Filter time motor
torque
0...20000 ms
46.14
Filter time power
out
0...20000 ms
Description
Defines a speed corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A or FBA B). For example,
with a setting of 500, the fieldbus reference range of
0...20000 would correspond to a speed of 500...[46.1]
rpm.
Note: This parameter is effective only with the ABB
Drives communication profile.
Speed corresponding to minimum fieldbus reference.
Defines a frequency corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A or FBA B). For example,
with a setting of 30, the fieldbus reference range of
0...20000 would correspond to a speed of 30...[46.2]
Hz.
Note: This parameter is effective only with the ABB
Drives communication profile.
Frequency corresponding to minimum fieldbus
reference.
Defines a filter time for signals
1.2 Motor speed
estimated,
and
1.5 Encoder 2 speed
Motor speed signal filter time.
Defines a filter time for signal
Output frequency signal filter time.
Defines a filter time for signal
Motor torque signal filter time.
Defines a filter time for signal
Output power signal filter time.
1.1 Motor speed
1.4 Encoder 1 speed filtered
filtered.
1.6 Output
frequency.
1.10 Motor
torque.
1.14 Output
power.
Def / Type
FbEq 16b / 32b
0.00 rpm / real32
1 = 1 rpm / 100 = 1
rpm
0.00 Hz / real32
10 = 1 Hz / 100 = 1 Hz
used,
500 ms / real32
1 = 1 ms / 1 = 1 ms
500 ms / real32
1 = 1 ms / 1 = 1 ms
100 ms / real32
1 = 1 ms / 1 = 1 ms
100 ms / real32
1 = 1 ms / 1 = 1 ms

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents