No.
Name / Range /
Selection
True
RO1
Other [bit]
33.24
On-time 2 warn
message
On-time 2 exceeded
Clean device
Maintain additional
cooling fan
Maintain cabinet fan
Maintain DC
capacitors
Maintain motor
bearing
33.30
Edge counter 1
actual
0...4294967295
33.31
Edge counter 1 warn
limit
0...4294967295
33.32
Edge counter 1
function
b0
Counter mode
b1
Warning enable
Description
Constant 1.
Bit 0 of
10.21 RO status (page
See
Terms and abbreviations (page
Selects the optional warning message for on-time timer
2.
A887 On-Time
2. The message text can be edited on
the control panel by choosing Menu – Settings – Edit
texts.
A88C Device
clean.
A890 Additional cooling
A88E Cabinet
fan.
A88D DC
capacitor.
A880 Motor
bearing.
Actual present value of signal edge counter 1.
The counter is incremented every time the signal
selected by parameter
switches on or off (or either, depending on the setting
of
33.32 Edge counter 1
applied to the count (see
When the counter exceeds the limit set by
counter 1 warn
limit, bit 2 of
to 1. The warning specified by
warn message
is also given if enabled by
counter 1
function.
The counter can be reset from the Drive Composer PC
tool, or from the control panel by keeping Reset
depressed for over 3 seconds.
Actual present value of signal edge counter 1.
Sets the warning limit for signal edge counter 1.
Warning limit for signal edge counter 1.
Configures signal edge counter 1.
0 = Loop: When the limit is reached, the counter is reset.
The counter status (bit 2 of 33.1) switches to 1 and
remains so until the counter is again incremented. The
warning (if enabled) stays active for at least 10 seconds.
1 = Saturate: When the limit is reached, the counter
status (bit 2 of 33.1) switches to 1, and remains so until
33.30
is reset. The warning (if enabled) also stays active
until
33.30
is reset.
0 = Disable: No warning is given when the limit is
reached
1 = Enable: A warning (see 33.35) is given when the limit
is reached
214).
169).
fan.
33.33 Edge counter 1 source
function). A divisor may be
33.34 Edge counter 1
33.31 Edge
33.1 Counter status
33.35 Edge counter 1
33.32 Edge
Parameters 391
Def / Type
FbEq 16b / 32b
1
2
On-time 2 exceeded
/ uint32
1
6
7
8
9
10
- / uint32
divider).
is set
- / -
- / uint32
- / -
- / uint16

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents