564 Parameters
No.
Name / Range /
Selection
85.79
Function type
Flowrate estimation
Head estimation
85.90
Q for the next
H-point
0.00 ... 30000.00
85.91
Flowrate actual
0.00 ... 30000.00
85.92
Head actual
0.00 ... 30000.00
85.99
Pump curves status
word
b0
DN zone
b1
UPT zone
b2...15
Reserved
0000h...FFFFh
Description
Selects the axis of Q-H pump curve that can be
interpreted as the output.
The user can choose the function to calculate either
actual Flow estimate out of input Head measurement
or actual Head estimate out of input Flow
measurement.
Function output is the flow estimate calculated from
the user given input interpreted as the total dynamic
head measurement.
Function output is the total dynamic head estimate
calculated from the user given input interpreted as the
flow measurement.
Displays the Flow value for the next missing Head point
in the custom user curve.
This signal serves for input assistance.
Q for the next H-point.
Displays actual flow rate calculated from the user
defined pump curve.
Note: In case parameter
Head
estimation, this signal displays the value used as
the input for the curve.
Flowrate actual.
Displays actual head calculated from the user defined
pump curve.
Note: In case parameter
Flowrate
estimation, this signal displays the value used
as the input for the curve.
Head actual.
Defines the pump curves status word.
Pump works in downthrust zone.
Pump works in upthrust zone.
85.79 Function type
is set to
85.79 Function type
is set to
Def / Type
FbEq 16b / 32b
Flowrate estimation
/ unit32
0
1
0.00 / real32
10 = 1 / 100 = 1
0.00 / real32
10 = 1 / 100 = 1
0.00 / real32
10 = 1 / 100 = 1
- / unit16
1 = 1