194 Parameters
No.
Name / Range /
Selection
6.18
Start inhibit status
word
b0
Not ready run
b1
Ctrl location
changed
b2
SSW inhibit
b3
Fault
b4
Lost start enable
b5
Lost run enable
b6
FSO inhibit
b7
STO
b8
Current calibration
ended
b9
ID run ended
b10
Auto phase ended
b11
Off1
b12
Em Off2
b13
Em Off3
b14
Auto reset inhibit
b15
Jogging active
0000h...FFFFh
6.19
Speed control status
word
Description
Start inhibit status word. This word specifies the source
of the inhibiting condition that is preventing the drive
from starting.
After the condition is removed, the start command
must be cycled. See bit-specific notes.
See also parameter
6.25 Drive inhibit status word
and
6.16 Drive status word
This parameter is read-only.
Note:
If bit 1 of
6.16 Drive status word 1
the removal of the inhibiting condition, and edge
triggering is selected for the active external
control location, a fresh rising-edge start signal
is required. See parameters 20.2,
If bit 1 of
6.16 Drive status word 1
the removal of the inhibiting condition, a fresh
rising-edge start signal is required.
Informative bit. The inhibiting condition need not
be removed by the user.
1 = DC voltage is missing or drive has not been
parametrized correctly. Check the parameters in groups
95
and 99.
1 = Control location has changed
1 = Control program is keeping itself in inhibited state
1 = A fault is active
1 = Start enable signal missing
1 = Run enable signal missing
1 = Operation prevented by FSO-xx safety functions
module
1 = Safe torque off active
1 = Current calibration routine has finished
1 = Motor identification run has finished
1 = Autophasing routine has finished
1 = Emergency stop signal (mode Off1)
1 = Emergency stop signal (mode Off2)
1 = Emergency stop signal (mode Off3)
1 = The autoreset function is inhibiting operation
1 = The jogging enable signal is inhibiting operation
Speed control status word.
This parameter is read-only.
1, bit 1.
is still set after
20.7
and 20.19.
is still set after
Def / Type
FbEq 16b / 32b
- / uint16
2,
1 = 1
- / uint16