Fieldbus control through the embedded fieldbus interface (EFB) 715
Bit
Name
2
OFF3_ CONTROL
3
INHIBIT_ OPERATION
4
RAMP_OUT_ ZERO
5
RAMP_HOLD
6
RAMP_IN_ ZERO
7
RESET
8
JOGGING_1
Value
STATE/Description
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined by drive
parameter. Proceed to OFF3 ACTIVE; proceed to
SWITCH-ON INHIBITED.
WARNING!
Ensure that the motor and driven machine
can be stopped using this stop mode.
1
Proceed to OPERATION ENABLED.
Note: Run enable signal must be active; see the
drive documentation. If the drive is set to receive
the Run enable signal from the fieldbus, this bit
activates the signal.
0
Inhibit operation. Proceed to OPERATION INHIB-
ITED.
1
Normal operation. Proceed to RAMP FUNCTION
GENERATOR: OUTPUT ENABLED.
0
Force Ramp Function Generator output to zero.
Drive ramps to stop (current and DC voltage limits
in force).
1
Enable ramp function.
Proceed to RAMP FUNCTION GENERATOR: ACCEL-
ERATOR ENABLED.
0
Halt ramping (Ramp Function Generator output
held).
1
Normal operation. Proceed to OPERATING.
Note: This bit is effective only if the fieldbus inter-
face is set as the source for this signal by drive
parameters.
0
Force Ramp Function Generator input to zero.
0=>1
Fault reset if an active fault exists. Proceed to
SWITCH-ON INHIBITED.
Note: This bit is effective only if the fieldbus inter-
face is set as the source for this signal by drive
parameters.
0
Continue normal operation.
1
Accelerate to jogging 1 reference.
Note:
• Bits 4...6 must be 0.
• See also section
0
Jogging 1 disabled.
Jogging (page
99).