386 Parameters
No.
Name / Range /
Selection
0.000 ... 30.000 s
32.219
Supervision 5 low
-21474830.00 ...
21474830.00
32.320
Supervision 5 high
-21474830.00 ...
21474830.00
32.225
Supervision 6 action
Disabled
Low
High
Abs low
Abs high
Both
Abs both
32.226
Supervision 6 action
No action
Warning
Fault
Fault if running
32.227
Supervision 6 signal
Zero
Other [value]
32.228
Supervision 6 filter
time
Description
Signal filter time.
Defines the lower limit for signal supervision 5.
Low limit.
Defines the upper limit for signal supervision 5.
Upper limit.
Selects the mode of signal supervision function 6.
Determines how the monitored signal (parameter
32.227 Supervision 6
signal) is compared to its lower
and upper limits (parameters
and
32.330 Supervision 6 high
is taken when the condition is fulfilled as selected in
parameter
32.226 Supervision 6
Signal supervision 6 is not in use.
A warning
(D20D Signal supervision
Action is taken whenever the signal rises above its
upper limit.
Action is taken whenever the absolute value of the
signal falls below its (absolute) lower limit.
Action is taken whenever the absolute value of the
signal rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low
limit or rises above its high limit.
Action is taken whenever the absolute value of the
signal falls below its (absolute) low limit or rises above
its (absolute) high limit.
Selects the action that drive takes when the value
monitored by signal supervision 6 exceeds its limits.
Note: This parameter does not affect the status
indicated by
32.200 Supervision
No action taken.
A warning
(D20D Signal supervision
The drive trips on fault code
6.
If running, the drive trips on fault code
supervision
6.
Selects the signal to be monitored by signal supervision
function 6.
None.
See
Terms and abbreviations (page
Defines a filter time constant for the signal monitored
by signal supervision 6.
32.229 Supervision 6 low
respectively). The action
action.
6) is generated.
status.
6) is generated.
D105 Signal supervision
D105 Signal
169).
Def / Type
FbEq 16b / 32b
1000 = 1 s / 1000 = 1
s
0.00 / real32
- / -
0.00 / real32
- / -
No action / uint16
0
1
2
3
4
5
6
No action / uint16
0
1
2
3
Zero / uint32
0
0.000 s / real32