AMT58x-DN DeviceNET®
4.8 Diagnostic LEDS
Two diagnostic LEDs located in the rear side of the connection cap
are designed to show the operating or fault status of the DeviceNet
interface and the system as well.
NS Led Network Status LED:
MS Led Module Status LED:
NS Led
OFF
Not powered or not on-line
Red
ON
Encoder communication failure
Flashing
red
Connection time-out
Green
ON
Device on-line and connected
Flashing
green
Device on-line but not connected
Flashing
green
/
Communication error
red
MS Led
OFF
No power supply
Red
ON
Unrecoverable fault (see attribute on page 44)
Recoverable fault, may need replacing (see
Flashing
red
attribute on page 44)
Green
ON
Device operational
Flashing
green
Device on-line but not connected (standby)
Flashing
green
/
Device self test
red
4.9 Bus termination
A bus termination resistance is provided in the connection cap.
This has to be activated as line termination in the last device.
Use RT Switch to activate or deactivate the bus termination.
RT
Activated: if the encoder is the last device in the
1 = 2 = ON
transmission line
Deactivated: if the encoder is not the last device in the
1 = 2 = OFF
transmission line