The maximum segment length for electrical data transmission with copper cables
between two nodes (field devices or switches) is 100 m. The copper cables are designed
uniformly in AWG 22. The installation guide defines different cable
types, whose range has been optimally adapted to general requirements for industry.
Sufficient system reserves allow industry-compatible installation with no limitation on
transmission distance.
The PROFINET cables conform to the cable types used in industry:
For complete information please refer to IEC 61918, IEC 61784-5-13 and IEC 61076-2-
101.
To increase noise immunity only S/FTP or SF/FTP cables must be used (CAT-5).
The maximum cable length (100 meters) predefined by Ethernet 100Base-TX must be
compulsorily fulfilled.
Regarding wiring and EMC measures, the IEC 61918 and IEC 61784-5-13 must be consid-
ered.

LINE TERMINATION

Profinet network needs no line termination because the line is terminated automati-
cally. Every Slave is able to detect the presence of the downstream Slaves.

MAC ADDRESS AND IP ADDRESS

The unit can be identified in the network through the MAC address and the IP address.
MAC address has to be intended as a permanent and globally unique identifier assigned
to the unit for communication on the physical layer; while the IP address is the name of
the unit in a network using the Internet protocol. MAC address is 6-byte long and can-
not be modified. It consists of two parts, numbers are expressed in hexadecimal nota-
tion: the first three bytes are used to identify the manufacturer (OUI, namely
Organizationally Unique Identifier), while the last three bytes are the specific identifier
of the unit. The MAC address can be found on the label applied to the encoder. The IP
address (and the subnet mask) must be assigned by the user to each interface of the
unit to be connected in the network. For additional information on the MAC address
refer to "
"
Setting the device name and the IP address" on page 26

GROUND CONNECTION

To minimize noise connect properly the shield and/or the connector housing and/or the
frame to ground. Connect properly the cable shield to ground on user's side. Datalogic's
EC- pre-assembled cables are fitted with shield connection to the connector ring nut in
order to allow grounding through the body of the device. Datalogic's CN- connectors
have a plastic gland, thus grounding is not possible. If metal connectors are used, con-
nect the cable shield properly as recommended by the manufacturer. Anyway make
sure that ground is not affected by noise. It is recommended to provide the ground con-
nection as close as possible to the device. We suggest using the ground point provided
in the cap (see Figure 1, use 1 TCEI M3 x 6 cylindrical head screw with 2 tooth lock wash-
ers).
PROFINET Type A: Standard permanently routed cable, no movement after instal-
lation
PROFINET Type B: Standard flexible cable, occasional movement or vibration
PROFINET Type C: Special applications: for example, highly-flexible, constant
movement (trailing cable or torsion)
MAC Address" on page 18
. For additional information on the IP address refer to
.
LINE TERMINATION
9
INSTRUCTION MANUAL