4.8 Baud rate: DIP A
WARNING
Power supply must be turned off before performing this operation!
Transmission rate can be set either via hardware or via software.
If DIP A bit 4 = "OFF" the bit rate is set through object
rate
in the "Object Dictionary" and can be modified using SDO
messages.
If DIP A bit 4 = "ON" the bit rate is set by DIP A.
DIP A:
Set binary value of transmission rate considering that: ON=1, OFF=0.
bit
1 LSB
0
2
Available baud rate values:
Decimal value
0
1
2
3
4
5
6
7
Example
Set 250Kbit/s:
4
= 100
(binary value, see table above)
10
2
bit
1
0
2
OFF
Set 500Kbit/s:
5
= 101
(binary value, see table above)
10
2
bit
1
0
2
ON
2
3 MSB
1
2
2
2
Binary value
000
001
010
011
100
101
500 Kbit/s (default)
110
111
2
3
1
2
2
2
OFF
ON
2
3
1
2
2
2
OFF
ON
AMT58x-CB CANopen®
3000-00 Baud
4
ON/OFF
Baud rate
20 Kbit/s
50 Kbit/s
100 Kbit/s
125 Kbit/s
250 Kbit/s
800 Kbit/s
1000 Kbit/s
4
3
2
ON
4
3
2
ON
11