363-206-285
Issue 2, February 2000
3.
NOTE:
Far-end alarm or status conditions are listed in this report with a Source
Address of farend. Local alarm or status conditions have a Source
Address of the local slot, line, port, channel, path, cross-connection, or
operations interface (DCC, TL1 (X.25), TBOS, etc.) where the event
occurred. (See Addresses in the Commands and Reports section of this
manual.) Use the rtrv-alm: command to get another report, if
necessary.
Does the Source Address of any top entry above the first single-dashed line
in the alarm report indicate a local alarm?
If YES, then continue with Step 4.
If NO, then proceed to Step 6.
4.
Find the Alarm Level for the local alarm in Table A and go to the indicated
procedure.
Table A – Trouble Conditions
Alarm Level
CRITICAL
MAJOR
MINOR
ne-acty
PWR MINOR (PMN)
abnormal (ABN)
5.
STOP. YOU HAVE COMPLETED THIS PROCEDURE.
6.
Use the rtrv-nmap/rtrv-map-network command to get a network map
report.
TAP
TAP-101
TAP-102
TAP-112
TAP-117
TAP-104
TAP-109
DDM-2000 OC-3 M
Trouble Clearing:
ULTIPLEXER
TAP-107
Page 2 of 28