DLP-536
: Detailed Level Procedure
Page 4 of 4
!
14.
DANGER:
A high discharge current is present at connector head if TESTING
indicator is lighted. Batteries must not be connected or disconnected
when TESTING indicator is lighted.
Depress test set STOP button. Proceed to Step 17.
Response:
15. After 15 minutes, the test set COMPLETE indicator lights.
16. Is any REPLACE indicator on test set lighted?
If YES, then continue with Step 17.
If NO, then STOP. YOU HAVE COMPLETED THIS PROCEDURE.
17. Unplug and set aside all defective batteries.
18. Install and connect replacement batteries to battery shelf. Reconnect any
remaining good batteries to battery shelf.
19. Place batteries on high charge by depressing HIGH RATE CHG ACTIVATE
pushbutton on BATTERY CHARGER and repeat from Step 6.
STOP indicator on test set lights