363-206-285
Issue 2, February 2000
17. Unseat and reseat SYSCTL to perform reset.
18. Is alarm still present?
If YES, then continue with Step 19.
If NO, then proceed to Step 21.
19. Has SYSCTL or OHCTL been replaced?
If NO, then continue with Step 20.
If YES, then proceed to Step 23.
20.
!
CAUTION:
Replacing the SYSCTL involves updating the internal memory on the
circuit pack.
Replace the SYSCTL or OHCTL.
Reference: DLP-523
21. Repeat program installation procedure.
Reference: DLP-532
22. STOP. YOU HAVE COMPLETED THIS PROCEDURE.
23. If you need technical assistance, notify your supervisor, your local technical
support organization, or call Lucent Technologies RTAC, per local operating
instructions.
24. STOP. YOU HAVE COMPLETED THIS PROCEDURE.
DDM-2000 OC-3 M
Trouble Clearing:
ULTIPLEXER
TAP-116
Page 5 of 6