62.3.5 SD devices

The SD devices are word devices into which GOT communication errors (error codes), clock data and other information
are stored.
List of SD devices
The following lists the SD devices (virtual devices inside the GOT).
Address
100ms counter (32bits)
SD0
SD1
Communication error status
*1
SD2
SD3
Clock data (second): Second data of 00 to 59 is stored.
SD4
Clock data (minute): Minute data of 00 to 59 is stored.
SD5
Clock data (hour): Hour data of 00 to 23 is stored.
SD6
Clock data (day): Day data of 01 to 31 is stored.
SD7
Clock data (month): Month data of 01 to 12 is stored.
Clock data (year)
SD8
Clock data (day of week)
SD9
SD10 to 15
*1
*2
POINT
POINT
POINT
The side where virtual devices are set
System: Set on the system side.
User: Set on the user side (by sending request messages from host or using the touch switches, etc. on the GOT).
62 - 8
62. MICROCOMPUTER CONNECTION (ETHERNET)
62.3 Device Data Area
The counter is incremented at 100ms intervals after GOT is turned ON.
(The time elapsed after GOT is turned ON is stored in 100ms units.)
(1) When setting the LH order to [32bit Storage] for the communication detail settings
The lower and upper bits are stored in SD0 and SD1 respectively.
Upper word
(2) When setting the HL order to [32bit Storage] for the communication detail settings
The upper and lower bits are stored in SD0 and SD1 respectively.
Upper word
An error data (error code) occurred during communication is stored.
•Host Address (Communication error that occurred on the request destination GOT)
0: No error
2: Framing error
4: Communication message error
6: Clock data setting error
•Other station (Communication error that occurred on another GOT when multiple GOTs are connected)
101: Parity error
103: Overrun error
105: Timeout error (No station of the specified address exists.)
106: Multiple units not connectable
4-digit year data is stored.
*2
Day-of-the-week data is stored.
0: Sunday
1: Monday
4: Thursday
5: Friday
For details and corrective actions for the errors (error codes) that are stored into SD2, refer to the following:
 Details and actions for errors (error codes) stored into SD2
If a wrong day of the week is set by the clock data setting command, the clock data will differ from the time displayed on the utility.
Example: When October 01, 2009 (Tuesday) is set by the clock data setting command (the actual day of the week is Thursday)
"2" is stored to SD9 although Thursday (THU) will be displayed on the utility time display.
Description
SD1
SD0
1: Parity error
3: Overrun error
5: Command error
102: Framing error
104: Communication message error
107: Clock data setting error
2: Tuesday
3: Wednesday
6: Saturday
Unused
SD0
Lower word
SD1
Lower word
Set side
System
System
-