11.10 H: Terminal Functions
Setting Value
Function
69
External Power 24V
Supply
6A
Data Logger Error
90
DWEZ Digital Output 1
91
DWEZ Digital Output 2
92
DWEZ Digital Output 3
93
DWEZ Digital Output 4
A0
DWEZ Extended Digital
Output 1
A1
DWEZ Extended Digital
Output 2
A2
DWEZ Extended Digital
Output 3
A3
DWEZ Extended Digital
Output 4
A4
DWEZ Extended Digital
Output 5
A5
DWEZ Extended Digital
Output 6
A6
DWEZ Extended Digital
Output 7
A7
DWEZ Extended Digital
Output 8
100
!During Run
101
!Zero Speed
102
!Speed Agree 1
536
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : The external 24V power supply is supplying power.
OFF : The external 24V power supply is not supplying power.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 1. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 2. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 3. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 4. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 1. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 2. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 3. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 4. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 5. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 6. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 7. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 8. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when you input a Run command and when the drive is outputting voltage.
ON : Drive is stopping
OFF : Drive is running
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency is less than E1-09 [Minimum Output Frequency] or b2-01 [DC
Injection/Zero SpeedThreshold].
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting
0
Open Loop V/f Control
1
V/f Control with Encoder
2
Open Loop Vector
3
Closed Loop Vector
4
Advanced OpenLoop Vector Control
5
PM Open Loop Vector Control
6
PM Advanced Open Loop Vector
7
PM Closed Loop Vector Control
8
EZ Open Loop Vector Control
ON : The output frequency is the value of E1-09 or more, or b2-01 or more.
OFF : The output frequency is less than the value of E1-09 or b2-01.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency is in the range of the frequency reference ± L4-02 [Speed
Agree Detection Width].
Note:
In CLV, the motor speed is the reference.
ON : The output frequency does not align with the frequency reference although the drive is running.
OFF : The output frequency is in the range of "frequency reference ± L4-02".
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
Parameter Used as the Reference
E1-09
E1-09
b2-01
E1-09
E1-09
E1-09
E1-09
b2-01
E1-09
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Ref.
844
844
844
844
844
844
844
844
844
844
844
844
844
844
844